Part Number Hot Search : 
ALVCH 641L2 DS1708 ZX84C8V2 1689M2 ZX84C18 1N5339BG ICS1702
Product Description
Full Text Search
 

To Download RCP-100011 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  specification - single unit rcp-1000-12 rcp-1000-24 model dc voltage rated current current range rated power output voltage adj. range line regulation load regulation setup, rise time hold up time (typ.) voltage range note.5 frequency range efficiency (typ.) input inrush current (typ.) leakage current ac current (typ.) 12v 24v 60a 40a 0 ~ 60a 0 ~ 40a 720w 960w 150mvp-p 11.6 ~ 12.4v 200mvp-p 23.2 ~ 24.8v 1.0% 1.0% 0.5% 0.5% 1000ms, 60ms/230vac at full load 16ms/230vac at full load 90 ~ 264vac 127 ~ 370vdc 47 ~ 63hz 81% cold start 50a 8.5a/115vac 4.5a/230vac 10.5a/115vac 5.5a/230vac 11a/115v ac 5.5a/230vac <1.1ma / 230vac rcp-1000-48 48v 21a 0 ~ 21a 1008w 300mvp-p 46.3 ~ 49.7v 1.0% 0.5% 0.5% 0.5% 0.5% universal ac input / full rangebuilt-in 5v/0.3a auxiliary power built-in active pfc function, pf>0.96 protections: short circuit / overload / over voltage / over temperature forced air cooling by built-in dc fan with fan speed control low profile:1u height active current sharing up to 3000w (3 units)in 19" rack, 3 racks max. can be operated in parallel (up to 8 units) remote control for single unitbuilt-in remote sense function output voltage trimming function hot-swap operation optional i c serial data bus ac ok & dc ok signal internal oring diode 3 years warranty ( note.7) 2 ripple & noise (max.) note.2 voltage tolerance note.3 87% 89% protection type : constant current limiting, recovers automatica lly after fault condition is removed over temperature overload over voltage 105 ~ 125% rated output power 13.2 ~ 16.2v protection type : shut down o/p voltage, re-power on to recover 75 5 (tsw1) detect on heatsink of power transistor 85 5 (tsw2) detect on heatsink of power diode protection type : shut down o/p voltage, recovers automatically after t emperature goes down 26.4 ~ 32.4v 52.8 ~ 64.8v protection selection guide single unit: rcp-1000- rack: rcp-1u whole system: rcp-3k1u - - i i 12 c - 12 c c: with i c interface c: with i c interface : without i c interface : without i c interface output voltage output voltage i: ac inlet(iec320-c14) i: ac inlet(iec320-c14) t: terminal block t: terminal block - - 2 2 2 2 1000 ~ 3000w front end power system features : r c p s e r i e s file name:rcp series-spec 2010-10-18
r c p s e r i e s note 1. all parameters not specially mentioned are measured at 230vac input, r ated load and 25 of ambient temperature. 2. ripple & noise are measured at 20mhz of bandwidth by using a 12" twisted pair- wire terminated with a 0.1uf & 47uf parallel capacitor. 3. tolerance : includes set up tolerance, line regulation and load regula tion. 4. the power supply is considered a component which will be installed into a fi nal equipment. the final equipment must be re-confirmed that it still me ets emc directives. 5. derating may be needed under low input voltages. please check the derati ng curve for more details. 6. output of all the rcp-1000 modules are connected in parallel in the rack. 7. under parallel operation of more than one rack connecting together, ri pple of the output voltage may be higher than the spec at light load condition. it will go back to normal ripple level once the output load is more than 10%. for guidance on how to perform these emc tests, please refer to ?emi testing of c omponent power supplies.? (as available on http://www.meanwell.com) specification - rack system rcp-3k1u -12 rcp-3k1u -24 rcp-3k1u -48 model voltage range note.5 module output voltage rack max. output current max. output power note.6 frequency range input output leakage current ac current (typ.)for each unit 90 ~ 264vac 127 ~ 370vdc 2160w 3024w 180a 63a 12v rcp-1ui or rcp-1ut 48v rcp-1000-12 rcp-1000-24 rcp-1000-48 47 ~ 63hz <3.5ma / 230vac 8.5a/115vac 4.5a/230vac 10.5a/115vac 5.5a/230vac 11a/115v ac 5.5a/230vac safety standards withstand voltage isolation resistance harmonic current ems immunity working temp. working humidity storage temp., humidity temp. coefficient vibration dimension packing others ul60950-1, tuv en60950-1 approved compliance to en55022 (cispr22) class b compliance to en61000-3-2,-3 compliance to en61000-4-2,3,4,5,6,8,11, env50204, en61000-6-2 (en50082-2), heavy industry level, criteria a -20 ~ +60 (refer to output load derating curve) 20 ~ 90% rh non-condensing -40 ~ +85 , 10 ~ 95% rh 0.02%/ (0 ~ 50 ) 10 ~ 500hz, 2g 10min./1cycle, 60min. each along x, y, z axes rack 483.6*350.8*44(l*w*h) environment i/p-o/p:3kvac i/p-fg:1.5kvac o/p-fg:0.7kvdc i/p-o/p, i/p-fg, o/p-fg:100m ohms / 500vdc / 25 / 70% rh emi conduction & radiation 11kg; 1pcs/11kg/2.67cuft file name:rcp series-spec 2010-10-18 ac fail signal ac fail signal dc ok signal dc ok signal remote sense remote sense remote on/off control remote on/off control auxiliary power auxiliary power the ttl signal out, refer to function manual the ttl signal out, refer to function manual compensate voltage drop on the load wiring up to 0.5v the ttl signal out, refer to function manual the ttl signal out, refer to function manual compensate voltage drop on the load wiring up to 0.5v. "local sense"shoul d be connected in order to get the correct output voltage if the "remote sense" is not used by electrical signal or dry contact on:short off:open by electrical signal or dry contact on:short off:open 5v @ 0.3a 5v @ 0.3a function function adjustment of output voltage, possible between 90 ~ 110% of rated output adjustment of output voltage, possible between 90 ~ 110% of rated output logic " high" for over temperature warning, refer to function manual logic " high" for over temperature warning, refer to function manual safety standards withstand voltage working temp. working humidity storage temp., humidity temp. coefficient vibration ul60950-1, tuv en60950-1 approved -20 ~ +60 (refer to output load derating curve) 20 ~ 90% rh non-condensing -40 ~ +85 , 10 ~ 95% rh 0.02%/ (0 ~ 50 ) environment i/p-o/p:3kvac i/p-fg:1.5kvac o/p-fg:0.7kvdc isolation resistance harmonic current ems immunity mtbf dimension packing others compliance to en55022 (cispr22) class b compliance to en61000-3-2,-3 43.4khrs min. mil-hdbk-217f (25 ) 295*127*41mm (l*w*h) safety & safety & emc (note 4) emc (note 4) i/p-o/p, i/p-fg, o/p-fg:100m ohms / 500vdc / 25 / 70% rh emi conduction & radiation 1.91kg; 6pcs/12.5kg/1.04cuft over temp warning over temp warning output voltage trim output voltage trim rcp-1000-12 rcp-1000-24 model rcp-1000-48 10 ~ 500hz, 2g 10min./1cycle, 60min. each along x, y, z axes compliance to en61000-4-2,3,4,5,6,8,11, env50204, en61000-6-2 (en50082-2), heavy industry level, criteria a 1000 ~ 3000w front end power system 2880w 120a 24v
mechanical specification (single unit) case no. 952a unit:mm pfc fosc : 110khz pwm fosc : 90khz input / output pin no. assignment(cn501) : cib24w9m400a1 connector postronic p pin no. pin no. pin no. pin no. 3,5,6 1,2,4 78 9 assignment assignment assignment assignment mating housin g -v +v on/off +s -s 12 17 22 13 18 23 14 19 24 11 16 21 10 15 20 sda scl a0 a1 a2 v_trim t_alarm ac_ok dc_ok cs +5v_aux gnd_aux fg ac/ l ac/ n postronic pcib24w9f400a1 block diagram direction dc ok ac ok air flow 41 24 46 127 12 34 5 7 9 10 12 13 15 16 18 19 21 6 22 24 23 cn501 295 svr51 r c p s e r i e s & pfc filter & rectifiers aux power (5v/0.3a) pfc control o.l.p. aux gnd oring diode share current current v_trim share o.v.p. 2 i c on/off rectifiers control on/off detection circuit dc_ok t_alarm ac_ok optional i c function 2 fan limiting active current inrush control ing i/p -v +v rectifiers & filter switch- power rectifiers filter emi pwm -s +s circuit detection power aux 1000 ~ 3000w front end power system file name:rcp series-spec 2010-10-18
address rcp-1ut rcp-1ui switch l a l b l c n a n b n c 10 8 cn500 mounting bracket fig1 cn500 1 14 13 25 air flow direction a b c + + - - 1 1 14 14 13 13 25 25 22 50 125 125 22 50 125 125 350.8 24 3-m5 l=6mm 3-m5 l=6mm dc ok dc ok dc ok ac ok ac ok ac ok 10.6 44 7.1 466.2 module c module b module a 483.6 440 31.8 6.1 address switch mechanical specification (rack system) case no. 959a unit:mm r c p s e r i e s 1000 ~ 3000w front end power system file name:rcp series-spec 2010-10-18
derating curve cn500 pin no. assignment cn500 in/out connector pins function description static characteristics load (%) input voltage (vac) 60hz 90 95 100 115 264 90 100 80 70 60 50 40 ambient temperature ( ) load (%) 20 40 60 80 100 -20 0 10 20 30 40 50 60 70 ta=25 r c p s e r i e s connector pin no. assignment(cn500) : d-type right angle 25 positi ons pin no. pin no. pin no. pin no. pin no. 2 13 4 5 assignment assignment assignment assignment assignment ac-ok-a on/off-a dc-ok-a v-trim-a t-alarm-a 7 13 9 8 10 14 15 6 12 11 16 17 23 21 22 25 18 19 20 24 ac-ok-b dc-ok-b on/off-b +5v-aux gnd-aux nc cs on/off-c v-trim-b t-alarm-b ac-ok-c dc-ok-c scl -s +v -v v-trim-c t-alarm-c +s sda pin no. function description 1,8,15 2,9,16 3,10,17 4,11,18 5,12,19 7 23 25 14 6 on/off ac-ok dc-ok v-trim t-alarm gnd-aux scl -v cs +5v-aux each unit can separately turn the output on and off by electrical or dry contac t between on/off a,b,c(pin 1,8,15) and -s(pin 21). short: on, open:off . low : when the input voltage is 82vrms +/-4v. high : when the input voltage in 82 vrms +/-4v. high : when the vout 80%+/-5%. low : when vout 80%+/-5% connection for output voltage trimming. the voltage can be trimmed wit hin its defined range. high : when the internal temperature is within safe limit. low : 10 below the th ermal shut down limit. auxiliary voltage output gnd. the signal return is isolated from the out put terminals (+v & -v). serial clock used in the i c interface option. refer to the i c interface descrip tion. negative output voltage. for local sense use only, can't be connected dir ectly to the load. current sharing signal. when units are connected in parallel, the cs pins o f the units should be connected to allow current balance between units. auxiliary voltage output, 4.3~5.3v, referenced to gnd-aux(pin 7). the maximum load current is 0.3a. this output has the built-in "oring diodes" and is not controlled by the remote on/off control. 2 2 1000 ~ 3000w front end power system file name:rcp series-spec 2010-10-18 20 21 +s -s positive sensing. the +s signal should be connected to the positive term inal of the load. the +s and -s leads should be twisted in pair to minimize noise pick-up effect. the maximum line drop compensation i s 0.5v. negative sensing. the -s signal should be connected to the negative term inal of the load. the -s and +s leads should be twisted in pair to minimize noise pick-up effect. the maximum line drop compensation i s 0.5v. 22 +v positive output voltage. for local sense use only, can't be connected dir ectly to the load. 24 sda serial data used in the i c interface option. refer to the i c interface descript ion. 2 2
function manual r c p s e r i e s 1. remote on/off control the psu can be turned on/off together or separately by using the "remote on/o ff" function. 2.1 remote sense output voltage can be trimmed between 90~110% of its rated value by the follo wing method. the remote sense compensates voltage drop on the load wiring up to 0.5v. 2.2 local sense notice : the +s,-s have to be connected to the +v,-v terminals locally in order t o get the correct output voltage if the remote sensing is not used. between on/off and -s sw open sw short output off on -s -s on/off a +v -v on/off a on/off b on/off b on/off c +s -s on/off c rcp-1u rcp-1u rcp-1u 1 22 25 1 8 8 15 20 21 15 21 21 2. voltage drop compensation -v +v rcp-1u +s -s load -v +v 3. output voltage trimming +s rcp-1u 20 -s 11 18 21 4 3.1 rcp-1000-12 r1 r1 r1 r2 r2 r2 v-trim-b v-trim-c v-trim-a 90 92 94 96 98 100 20 21 sense lines should be twisted in pairs vout (%) 180k 240k 350k 560k 1.2m nc r1 ( ) min. 0.1w 100 102 104 106 108 110 vout (%) nc 300k 120k 62k 31k 13k r2 ( ) min. 0.1w 1000 ~ 3000w front end power system file name:rcp series-spec 2010-10-18
r c p s e r i e s function ac-ok ac-ng dc-ok dc-ng t-ok t-alarm led on off on off ---- ---- description when input voltage 82v 4v when input voltage 82v 4v when output voltage 80% 5% of vo rated. when output voltage 80% 5% of vo rated. when the internal temperature (tsw1 & tsw2 short) is within safe limit when the internal temperature (tsw1 or tsw2 open) exceeds the limit of tem perature alarm 4. front panel indicators & corresponding signal at function pins 5. i c bus interface option 5.1 addressing(a0,a1,a2) the dip switch down position is logic level "1" and the up position is level "0" . address are applicable when modules rcp-1000 i c function are used. address dip switch setting on 1 2 module a module b module c 3 4 5 6 7 8 9 off 2 2 signal 0 ~ 0.5v 4.5 ~ 5.5v 0 ~ 0.5v 4.5 ~ 5.5v 0 ~ 0.5v 4.5 ~ 5.5v psu output on off on on on off * *signal between function pin and "-s". 3.3 rcp-1000-48 90 92 94 96 98 100 vout (%) 1.3m 1.7m 2.4m 3.6m 7.6m nc r1 ( ) min. 0.1w 100 102 104 106 108 110 vout (%) nc 345k 140k 70k 36k 15k r2 ( ) min. 0.1w a2 36 9 a1 25 8 a0 14 7 module ab c 1000 ~ 3000w front end power system file name:rcp series-spec 2010-10-18 3.2 rcp-1000-24 90 92 94 96 98 100 vout (%) 560k 750k 1m 1.6m 3.3m nc r1 ( ) min. 0.1w 100 102 104 106 108 110 vout (%) nc 330k 130k 62k 30k 10k r2 ( ) min. 0.1w
r c p s e r i e s 6. analog function (read only) 7.eeprom function (read only) 6.1 analog function are provided by a single pcf8591 4-channel 8-bit a/ d converter. when this device is read by the i c bus controller, it provides an 8-b it 6.2 a/d scaling the eeprom is a 2048 bit (256 byte) device which is preprogrammed at the factor y with the following data : word with the following information: the voltage reading is made inside the power supply unit before the "oring di ode" and is typically 0.5v higher than the actual output voltage. the following table for the scaling should be employed: value = byte value x resolution pcf8591 slave address pcf8591 control byte 2 34 bit bit output voltage address 12v 4 12v 56 12v 104 24v 20 24v 72 24v 254 48v 40 48v 88 48v range bytes 0~16v 16 16 16 16 16 16 0~33v 20 0~65v 0~80a 0~55a 0~30a 0~100 0~100 2 0~100 scaling data 0.0625v/bit manufacturer serial number revision country of production model name output voltage date of production check sum 0.129v/bit 0.254v/bit 0.312a/bit 0.215a/bit 0.117a/bit 0.391 /bit 0.391 /bit 0.391 /bit tolerance 5% a/d channel 1 a/d channel 2 a/d channel 3 voltage current temperature +3%,-5% +2%,-5% 10% 10% 10% 3 3 3 value value 2 1 a/d channel function output voltage output current internal temperature not used 77 10 6 5 6 5 0 0 0 0 44 10 33 a2 0 0 22 a1 11 a0 00 00 1 01 0 : output voltage : output current : internal temperature r/w 1000 ~ 3000w front end power system file name:rcp series-spec 2010-10-18 5.2 digital function (read only) digital function are provided by a pcf8574 8-bit i/o port device. when this d evice is read by the i c bus controller, a single 8-bit word provides the following information. bit function good state fail state meaning input power fail output voltage is less than specification internal temperature is over 60 . psu turns on temperature exceeds nominal operating limit. psu turns off failure of an internal fan not used not used not used 0 1 11 1 1 00 0 0 ------ ------ ------ ------ ------ ------ 0 ac input fail 1 output power good / fail 2 temperature warning 3 over temperature protection 4 fan fail warning 5 not used not used not used 67 2 eeprom slave address bit 7 6 5 4 3 2 1 0 value 1 0 1 0 a2 a1 a0 r/w pcf8574 slave address bit 7 6 5 4 3 2 1 0 value 0 1 0 0 a2 a1 a0 r/w read : 1 write : 0


▲Up To Search▲   

 
Price & Availability of RCP-100011

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X